Hydro Electric Project, Matatila
Installed capacity - 3 x 10.2 = 30.6MW
No. of units - 3
Sailent Features
Matatila Power Station is located in Lalitpur district (UP), 60 K.m. far from Jhansi City. Nearest Railway Station is Jhansi on the Delhi-Bombay route.
Power Station is situated at the left bank of river Betwa, which rises from Bhopal in the Vindhyan Plateau at an elevation of 1550ft, passes through granite rocks at a steep gradient, the river flows on outskirts of distt. Jhansi, forming boundary line of U.P. and M. P and thereafter it mostly flows in U.P., meeting the river Yamuna in Hamirpur Distt in U.P.
It is entirely a rain-fed river with very high discharge of water during rainy season and extremely low discharge during summers. The dam was constructed in year 1957 for irrigation purposes. Matatila Power House with three machines of 10.2 MW each on the existing dam was commissioned in 1965.
Hydrology
Catchment Area - 8000 Sq. Miles.
Reservoir Capacity at - 40000 M. Cu. Ft. Full level (R L 1012ft)
Climatic Data
The Climate of Matatila dam is very hot in summer season and some time temperature rises upto 50ºC during summer and very cold during winter season. There is monsoon rains in summer season only The climate is dry in rest of the year.
DAM
Masonary dam flanked by earthen embankments on either side.
| Height | 104.0 ft |
| Crest Length | 1,394.0 ft |
| Crest Width | 534.0 ft |
| Maximum Width at base | 1,394 ft |
| Spillway gate | 23 Nos |
| Size of gate | 60'x23' |
| Type of gate | Radial |
| Water Conducter System | Through Penstock |
DETAILS OF INTAKE STRUCTURE (Including type, number and size of gate)
| Particulars | Height | Length | Width | Still Level |
|---|---|---|---|---|
| Intake gate | 20' | 11'-8" | 1'-8" | 942' |
| Stop Log gate | 5' (5 Nos) 3'-8" (1 No.) |
15'-6" | 2' | 942' |
| Draft Tube gate | 14'-4" | 9'-3" | 1'-8"quot; | 886' |
Penstock
| Type | Cylindrical Steel Pipe |
| No. of Penstock | 3 |
| Dia | 11'-3" |
| Length | 210 ft |
Two pipe lines of Jal Nigam are connected with penstock of Machines for drinking water supply to Jhansi city.
Building
Power station building is located at left bank of the Dm, Length of the building is 205 meters, Width - 76.5 meters, Height - 109 meters, Control room of power house is located at left side of the building.
. Type of Control Board - Relay logic type
. Type of protection board - Mechanical relay Type
. Type of recorder - Analogue Type
Above mentioned boards are installed in control room.
Head & Design Discharge
| (1) Gross maximum head | 102 ft |
| (2) Gross Minimum head | 60 ft |
| (3) Discharge at Max. head | 1659 Cusec. |
Installed Capacity & Number of Units
| (1) Installed Capacity | 3x10.2 = 30.6 MW |
| (2) Number of Units | 3 Nos |
Turbine
| (a) Type of Turbine | Vertical Shaft Kaplan Turbine |
| (b) Output at max. head | 16,500 BHP |
| (c) Discharge at Max. head | 1655 Cusec |
| (d) Number of Runner blades | 6 Nos |
| (e) Specific Speed | 115.6 |
| (f) Efficiency at full load | 89.4% |
| (g) Guide vane | 20 Nos |
| (h) Material Shaft | Forged Steel |
| (i) Dia of Shaft | 19.75" |
| (j) Max. Run away speed | 675 rpm |
RUNNER
| (a) No. of Runner blades | 06 Nos |
| (b) Material of blades | 13 chromium cast steel |
| (c) Material of Runner boss | Low magnetic steel |
| (d) Internal dia | 98 ½" |
| (e) Velocity of Runner Unit | 40.1 EPS |
GOVERNOR
| (a) Type | Hitachi Cabinet type speed governor |
| (b) Range of adjustment of speed level | 0.6 |
| (c) Guaranteed Sensitivity | 0.1% |
| (d) Closing time of guide vanes | 7.2 Seconds |
| (e) Opening time of full gate | 15 Seconds |
Type of Generator & Excitation System
Generator
| (a) Capacity | 12000 KVA |
| (b) R.P.M. | 250 |
| (c) Full Load current | 630 Amp. 3$ |
| (d) Generating Voltage | 11 KV |
| (e) No. of Poles | 24 |
| (f) Power factor | 0.85 |
| (g) Efficiency at full load | 96.45% |
| (h) Insulation class | 'B' |
| (i) Outer dia of stator | 177" |
| (j) Generator air Gap | 1" |
| (k) Field current | 400 amp |
Main Excitor
| (a) Capacity | 120KW |
| (b) Full load voltage | 220V |
| (c) Ampere | 546amp |
| (d) Exciting Voltage | 110V |
| (e) Field | Separate |
| (f) Insulation Class | 'A' |
Pilot Excitor
| (a) Capacity | 5 KW |
| (b) Full Load Voltage | 110 v |
| (c) Ampere | 45.5 Amp |
| (d) Field | Compound |
| (e) Insulation Class | 'A' |
A.V.R
| (a) Type | Thyristor control Regulator type |
| (b) DC Control Voltage | 110 V ± 5% |
Details of The Tailrace
| (a) Type | Open Channel |
| (b) Intake crest length | 60' |
| (c) Maximum level | 913' (Normal) |
| (d) Minimum level | 908 |
| (e) Length | 10 meter (Appx) |
| (f) Width | 35 meter (Appx) |
| (g) Draft tube gate | 06 Nos |
Firm Power and Annual Energy Generation
| (a) Firm power | 9.56 MW |
| (b) Peaking Capacity during mansoon | 30.6 MW |
| (c) Peaking capacity during summer | 19.0 MW |
| (d) Firm output | 81.65 MU |
| (e) Seasonal output | 41.928 MU |
Details of Switch Yard
| (a) Size & Type | Open |
| (b) Transmission voltage | 66 KV and 11 KV |
| (c) No. of Bay | 01 |
| (d) Incomers | 03 |
| (e) Outgoing feeder | 05 |
Name of Outgoing Feeder
| (a) 66 KV Jhansi feeder | 02 Nos (25 MVA each) |
| (b) 66 KV MP (Pichhore) feeder | 01 No (5MW) |
| (c) 66 KV RORA feeder | 01 No. (2MW) |
| (d) 66 KV Lalitpur feeder | 01 No (5MVA) (Disconnected at present) |
Name of Incomers
| (a) No. of M/C | 03 Nos. |
| (b) M/C load | 10.2MW (each) |
TRANSFORMER
Generating TIF - 03 Nos
| (a) Capacity | 12000KVA (Make- Toshiba) |
| (b) Volts | 11/66KV |
| (c) Current | 630/105 Amp |
| (d) Phase | 3 $ |
| (e) Vector symbol | YD 11 |
| (f) Type of cooling | ON |
| (g) Impedance | 7.68% |
| (h) Capacity of oil | 2160 Gallons |
| (i) Weight of Oil | 8.874 TONS |
| (j) Total Weight | 34.1 TONS |
| (k) Tape Changer | No load type (off load) |
2MVA T/F (66/11KV) - 2 Nos
| (a) Make | Crompton & Parkinson |
| (b) Capacity | 2000 KVA |
| (c) Volt | 66/11 KV |
| (d) Current | 17.5/105 amp |
| (e) Type of Cooling | ON |
| (f) Impedance | 7.51% |
| (g) Vector Symbol | YD 11 |
| (h) Weight of oil | 4640 KG |
| (i) Oil Capacity | 5470 Lit |
UNIT AUXILIARY T/F - 03 Nos and station T/F - 02 Nos
| (a) Make | ECE |
| (b) Capacity | 300 KVA |
| (c) Volts | 11/0.4 KV |
| (d) Current | 15.75 amp/432.8 amp |
| (e) Type of Cooling | ON |
| (f) Impedance | 4.7% |
| (g) Vector Symbol | DY 11 |
| (h) Oil Weight | 650 Lit. /570 Kg |
BREAKER - Make HEL Bhopal
| (a) Type | LG 3C/66 (Bulk oil type) 66 KV Breaker |
| (b) Voltage | 66 KV |
| (c) Current Capacity | 800 amp |
| (d) Breaking capacity | 13.1KA, 3 Sec. |
| (e) Making capacity | 33.4 KA |
| (f) Closing/Tripping Coil Voltage | 110 V DC |
For 66 KV MP (Pichhore) feeder Breaker - 01 No
| (a) Type | SF-6 |
| (b) Voltage | 66 KV |
| (c) Make | ASEA |
| (d) Making Capacity | 45 KA |
| (e) Breaking capacity | 17.5 KA |
SIZE OF SWITCH YARD
| (a) Size of Switchyard | 160' x 100' |
| (b) Size of Transformeryard | 80' x 129' |
Total Project Cost / Cost of Generation
(1). (a) Net cost of Generation (F.Y. 2000-01) - 17.28 Paise per Unit
(b) Total Project cost - 416.009 Lacs
(2). Unit wise details of the machines as per name plate for both turbine and Generator:-
ACTUATOR GENERATOR
For 12000 KVA Actuator
RPM --250
MFG. No.-- 106464
Date-- 1963
DC Generator
| RPM-250 Code- BSS | RPM- 250 Code- BSS |
| Main Exciter | Pilot Excitor |
| Kw- 120 Type- VFB Form -SP | Kw 5 Type-VB. Form -K |
| Full Load Volt - 220 AMPS - 546 | Full Load Volt - 110 AMPS- 45.5 |
| Exciting Volts - 110 Rating - Cont | Field - Comp Rating - cont |
| Field - Separate | Insulation Class -A |
| Insulation Class A | Date 1963 |
| Mfg no. -253166 Date -1963 |
Alternating Current Generator
| Type - VEFKW | Form - RD | Code | BS:- 2613 |
| KVA- 12000 | RPM- 250 | Phases -3 | Poles- 24 |
| Volts- 1000 | AMPS- 630 | Cycles- 50 | PF 0-85 |
| Main Ex.KW -120 | Main Ex.Volt- 220 | Main Ex. AMP- 443 | |
| Mfg. No- 106461-1 | Date -1963 | ||
| Pat No. -367954, 374078, 393066, 401955 | |||
Water Turbine
| TYPE --VK | FORM-- IRS | |
| EFFECTIVE HEAD | DISCHARGE | OUTPUT |
| MAX. 99 ft | 1655 cfs | 16500 HP |
| NOR. 85 ft | 1655 cfs | 14250 HP |
| MIN. 58 ft | 1415 cfs | 8000 HP |
| RPM 250 | CODE BS353 | DATE 1963 |
| MFG NO. 141281-1 | PAT NO. 205210 | |
| TOKYO Hitachi Ltd | JAPAN WP = T2453 |
(5). General information in respect of Generation from the units and auxiliary consumption.
(a) Details of annual generation of last 6 years.
1996-97 - 131.172 MU
1997-98 - 157.997 MU
1998-99 - 132.805 MU
1999-00 - 160.909 MU
2000-01 - 138.083 MU
2001-02 - 140.203 MU
(b) Auxiliary consumption of the plant is approximately 0.2% of Generation.
(6). Schedule for annual maintenance
Annual maintenance of one M/C of Matatila Power House is being done each year for smooth Running of M/c's as per instructions issued earlier.
(7). R.L.A & L.E. of Matatila Power House is proposed to be carried out by M/S BHEL and order for the same has already been placed.
(8). An E.O.T crane of 80 ton capacity has already been installed in Power House for dismantaling and erection Works. A mechanical workshop having lathe M/C, Shapers, drill M/C & Welding M/C has also been installed in Matatila Power House.
Single Line Diagrame of Matatila Power House